Smart Integrated Cabinet Generation 1

Compliant with international standards ISO 12944, Data Center Design Code (GB 50174-2017), Comprehensive Cabling System Engineering Design Code (GB/T 50311-2016), Building Fire Protection Code (GB50016–2014), General Specifications for Electronic Computer Room Sites (GB/T 2887-2000), Security and Protection Engineering Technical Code (GB50348—2018), Building Lighting Design Standard (GB50034-2013), Flame-Retardant and Fire-Resistant Flexible Cables for Communication Power Supplies (YD/T 1173-2016), and Lightning Protection and Grounding Engineering Design Code for Telecommunication Stations (YD5098-2005). Also compliant with GB 4943.1 and GB 4943.23 for Information Technology Equipment Safety, as well as GB/T 1804 for general tolerances—specifically, linear and angular tolerances without specified tolerances, using the m-grade standard—and GB/T 1184 for geometric tolerances, where no tolerance values are indicated, applying the K-grade standard.

Product Details

Item

Description

Single Cabinet

Cabinet Array (Supports up to 1-to-7 configuration)

Overall Parameters

Power Supply Standard

220Vac, 380Vac

Operating Environment

0~40℃

Altitude

0~4000m (Derating required above 2000m)

Cabinet System

Cabinet Dimensions (W*H*D)

600mm*2000mm*(1200-1400)mm

(600~4200)mm*2000mm*(1200-1400)mm

Power Distribution System

System Input

Main Input Switch

Supports single/dual circuits 32A/63A

Supports single/dual circuits 32A/63A/100A/200A/250A

System Output

Output Circuits

UPS Input, UPS Output, UPS Bypass, PDU Output, Cooling Output, etc.; Circuit Breakers: 16A~100A

UPS

Capacity

3KVA/6KVA

6KVA~30KVA

Configuration

Single UPS

Single/Dual UPS

Power Factor

≥0.9

Efficiency

≥94%

Backup Power

Lead-acid battery pack, lithium battery pack, lead-acid battery, battery rack, battery cabinet

Cooling System

Rack-Mounted Air Conditioner

3.5KW/4.2KW/8.1KW/12.5KW cooling capacity, configured with N+1 redundancy. Outdoor unit: -40℃~45℃, indoor unit: 18℃~40℃. DC Inverter EC compressor, variable-frequency indoor/outdoor fans; all piping features quick-connect fittings, no welding required; pipe length customized based on on-site measurement.

Monitoring System

Monitoring Functions

10.1-inch touchscreen with power distribution monitoring, UPS monitoring, battery monitoring, switching power supply monitoring, temperature/humidity monitoring, smoke detection, water leakage detection, refrigeration monitoring, access control monitoring, etc.; includes system management, monitoring management, real-time data, historical data, and other management functions.

Optional Components

Component Name

Smart Access Control, SMS Alerts, Video Surveillance, Low-Temperature Components, Air Conditioning Duct Extension Components, Centralized Management Platform, ATS Module, etc.