GGD Low-Voltage Complete Fixed-Type Switchgear
Product Categories:
Product Details
Overview

Operating Conditions
- The ambient air temperature shall not exceed +40°C or be lower than -5°C, and the 24-hour average temperature shall not exceed +35°C;
- For indoor installation and use, the altitude of the installation site shall not exceed 2000m;
- The relative humidity of the ambient air shall not exceed 50% at the maximum temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at +20°C), taking into account the occasional condensation caused by temperature changes;
- The inclination angle between the equipment and the vertical plane during installation shall not exceed 5°;
- The equipment shall be installed in a location free from severe vibration, shock, and environments that could cause corrosion to electrical components;
- For special user requirements, solutions can be negotiated with the manufacturer.
Technical Parameters