Overview
Model Meaning

Operating Conditions
- Altitude: Not exceeding 1000 meters;
- Ambient temperature: -35°C ~ +40°C;
- Relative humidity: Daily average not greater than 95%, monthly average not greater than 90%;
- Installation site: Locations free from fire, explosion hazards, and chemically corrosive gases, with good ventilation; the ground inclination angle shall not exceed 3°.
Functions and Features
- Fully insulated, fully sealed, maintenance-free or low-maintenance, reliably ensuring personal safety;
- Compact structure: its volume is only 1/3 to 1/5 of that of European-style transformers with the same capacity, and its height is lower;
- A split-box structure can be adopted to avoid oil contamination inside the transformer oil tank;
- Double-fuse full-range protection is used on the high-voltage side, greatly reducing costs;
- Can be used in both ring networks and terminals; the cable head can be plugged and unplugged emergently under a 200A load current;
- The cabinet body is made of stainless steel material, with both heat insulation and heat dissipation functions;
- An electronic phase-loss protector is installed on the low-voltage side; when abnormal voltage occurs in the system, it can quickly trip the main incoming switch;
- The oil-immersed load switch on the high-voltage side can be upgraded to electric operation, laying a foundation for realizing distribution network automation;
- Uses oil-immersed S11 transformers or higher-performance S13 series transformers;
Technical Parameters
Item | Unit | Parameter |
Rated Voltage | kV | 10/0.4 (High Voltage/Low Voltage) |
Maximum Operating Voltage Rated Frequency Rated Capacity 1-Minute Power Frequency Withstand Voltage | kV | 12 (High Voltage Side) |
Hz | 50 | |
kVA | 50-1600 | |
kV | 42 | |
Lightning impulse voltage | kV | 75 |
Cooling method |
| Oil-immersed self-cooled |
High-Voltage Backup Fuse Breaking Capacity | kA | 50 |
Plug-in Fuse Breaking Capacity | kA | 2.5 |
Ambient Temperature | ℃ | -35~+40 |
Allowable Coil Temperature Rise | ℃ | 65 |
No-Load Voltage Regulation |
| ±5% or ±2x2.5% |
Noise Level | dB | 50 |
Protection Rating |
| IP33 |
Item | Unit | FKN12-12 Load Switch | FZN25-12 Vacuum Load Switch |
Rated Voltage | kV | 10 | |
Maximum Operating Voltage | kV | 12 | |
Rated Frequency | Hz | 50 | |
Rated Current | A | 630 | |
Rated Breaking Capacity | A | 630 | |
Thermal Stability Current (RMS) | kA/s | 20/2 | 20/4 |
Dynamic Stability Current | kA | 50 | 50 |
Short-Circuit Closing Current (Peak) | kA | 50 | 50 |
Full-Load Breaking Cycles | Cycles | 2000 | 10000 |
Mechanical Life | Cycles | 2000 | 10000 |
Power Frequency Withstand Voltage (Phase-to-Phase and Phase-to-Ground) | kV | 42 | 42 |
Lightning impulse voltage (phase-to-phase and phase-to-ground) | kV | 75 | 75 |